DC Testing of OPI-type 400 kV Bushings
Tadeusz GLINKA
Abstract
High voltage (HV) power transformers are equipped with OPI-type bushings (oil-paper insulation). Insulation diagnostic aging tests are based upon tanδ measurements. Engineering practice shows that tanδ does not provide reliable information on bushing technical condition. This statement is substantiated by bushing failures, including fres. The inner layers of paper exhibit local charrings caused by partial discharges; these are not indicated by tanδ measurements. The following issues are presented in the paper: bushing design, equivalent scheme of insulation core, off-line DC test procedures and results of tests of two bushings.
Keywords
HV transformers, bushings, OPI, diagnostics
Fig.
Bilbiography
[1] B. Drak, T. Glinka, J.Kapinos, R. Miksiewicz, P. Zientek P.: „Awaryjność maszyn elektrycznych i transformatorów w energetyce.”Instytut Napędów i Maszyn Elektrycznych KOMEL w Katowicach 2013 r.
[2] T. Glinka, S. Szymaniec: „Eksploatacja i diagnostyka maszyn elektrycznych i transformatorów.” PWN 2019 r.
[3] M. Kaźmierski, W. Olech: „Diagnostyka techniczna i monitoring transformatorów.” Energopomiar – Elektryka. Gliwice 2013 r.
[4] W. Latek: „Badanie maszyn elektrycznych w przemyśle. „ WNT, 1979. Rozdział 5 Badanie transformatorów.
[5] Ramowa Instrukcja Eksploatacji Transformatorów. Energopomiar – Elektryka. Gliwice 2012 r.
[6] Monografa „Teoria mocy, ochrona środowiska i eksploatacja w elektroenergetyce" s. 25-31, INFOTECH, 2019